- checkpoints inspected
- 74
- very-high and high-risk findings
- 26
- generator earth vs 1 Ω limit
- ≈3.4 Ω
- thermal hot spots found
- 7
The challenge
A testing laboratory needed an independent electrical safety audit of its substation, generators and distribution boards. There was no single-line diagram on site and no record of maintenance or testing, so nobody could say with confidence how the installation was protected.
Our approach
Our engineers inspected the installation against a 74-checkpoint register based on BNBC 2020, NFPA 70 (NEC 2014) and NTPA, photographing every non-conformity. We backed the inspection with instrument tests:
- a thermographic survey of panels and terminations with a Fluke Ti110, classified by temperature rise
- earth resistance tests on system, equipment and generator earthing with a Hioki FT6380 clamp-on tester
- insulation-resistance tests on cables with a Sanwa MG-1000 at 1000 V and 500 V for 60 seconds, following BS 7671 procedures
The result
About 42% of the 74 checkpoints were compliant. The register identified 5 very-high-risk and 21 high-risk non-conformities, and the thermal survey found 3 major hot spots and 4 deficiencies. Generator earth pits measured about 3.4 Ω against a 1 Ω limit, and the site had no lightning protection. Cable insulation results were acceptable. The client received a ranked corrective action plan so the most dangerous items could be fixed first.
Why it matters
An earth that is above the limit may not carry enough fault current to trip the protection quickly, which leaves metalwork live for longer than it should be. Without a single-line diagram, maintenance staff cannot be sure what a breaker isolates. And a termination that is overheating looks normal until a thermal camera is pointed at it under load.
What the client received
- A 74-checkpoint register with a photograph and a risk rating for every non-conformity
- A thermographic survey report with hot spots classified by temperature rise
- Earth resistance and insulation-resistance test sheets for every point tested
- A corrective action plan ranked from Very High to Low, presented to the client's team