Gas boilers running below nameplate: what we measure and the cheapest fixes

A boiler rated at 80% measured about 73%, with only about 4% of condensate returned. The first fixes are low-cost: combustion tuning and bringing the condensate back.

By Rubel Mahmud, CEO & Team Leader

Boilers are one of the largest gas users in a garment or textile factory, and one of the easiest to lose efficiency without noticing. In a recent assessment, a 313 kg/hr gas-fired boiler rated at 80% efficiency measured about 73%, and only about 4% of the condensate was being returned to the boiler house.

How we measure it

  1. Step 1

    Loading test

    We run the boiler at a steady load for about an hour and record steam output, fuel and feedwater.

  2. Step 2

    Flue-gas analysis

    Oxygen, CO and flue temperature give the combustion efficiency and the stack loss.

  3. Step 3

    Indirect method

    Efficiency is calculated from the individual losses: stack, radiation, blowdown, so we know where the energy goes, not just the total.

  4. Step 4

    Thermal imaging

    A thermal camera finds uninsulated valves, flanges and leaks on the steam lines.

Why efficiency drops

  • Excess air drifting upward as burners go out of tune
  • Scale and soot on heat-transfer surfaces
  • Uninsulated valves and flanges radiating heat
  • Condensate dumped to drain instead of returned hot to the feed tank

The cheapest fixes come first

Combustion tuning costs very little and often recovers several points of efficiency. Returning condensate saves both the heat in the water and the treatment chemicals for make-up water. Insulating valves and flanges is next. Together, measures like these were enough to bring the plant in our example back to about 80%.

What it is worth

Moving a boiler from 73% back to 80% efficiency cuts its gas use by close to a tenth for the same steam. On a boiler that runs every working day, tuning and insulation often pay for themselves within months.

Signs your boiler needs attention

  • Flue-gas temperature that has crept up since the last service
  • Steam or hot water visible at drains and traps
  • Bare valves and flanges that are too hot to touch
  • Make-up water consumption close to steam output
  • No record of a flue-gas test in the last year

Rubel Mahmud

CEO & Team Leader · M.Sc. EEE (BUET) · SREDA Certified Energy Auditor

Electrical engineer who leads Raaida's audit, safety and design work, and the technical lead behind the Rumara audit platform.

More insights

Start a conversation

Discuss your project with an engineer

Tell us about the site and what you need. An engineer will reply within one working day.