Skip to content
Raaida Engineering

Free tool

Distribution board load calculator

Estimate connected load, maximum demand, current and a suggested incomer rating for a three-phase distribution board in a few minutes.

Connected load (kW)
0
Maximum demand (kW)
0
Apparent power (kVA)
0
Line current (A, 3-phase)
0
Suggested incomer (A)
0

Estimate only. Final protection must account for cable rating, fault level and discrimination.

How the calculator works

For each load, connected power is quantity × rated kW. Maximum demand applies the demand factor you enter, because not every load runs at full power at the same time. The total demand in kW is divided by the power factor to give kVA, and the line current for a balanced three-phase supply is kVA × 1000 ÷ (√3 × voltage).

The suggested incomer is the next standard breaker size above 1.25 × the calculated current. It is a starting point only: final protection must consider cable rating, fault level and discrimination.

Need a full load schedule and SLD? See our MEP design service.

Start a conversation

Need a full design, not an estimate?

Our engineers prepare load schedules, SLDs and BoQs to BNBC for factories and buildings.