Free tool
Distribution board load calculator
Estimate connected load, maximum demand, current and a suggested incomer rating for a three-phase distribution board in a few minutes.
- Connected load (kW)
- 0
- Maximum demand (kW)
- 0
- Apparent power (kVA)
- 0
- Line current (A, 3-phase)
- 0
- Suggested incomer (A)
- 0
Estimate only. Final protection must account for cable rating, fault level and discrimination.
How the calculator works
For each load, connected power is quantity × rated kW. Maximum demand applies the demand factor you enter, because not every load runs at full power at the same time. The total demand in kW is divided by the power factor to give kVA, and the line current for a balanced three-phase supply is kVA × 1000 ÷ (√3 × voltage).
The suggested incomer is the next standard breaker size above 1.25 × the calculated current. It is a starting point only: final protection must consider cable rating, fault level and discrimination.